Skip to content

Waterproofing Installation Inspection

Checklist for inspecting waterproofing and moisture barrier installation per ICC, ASTM, and manufacturer standards.

7 items to check

These checklists are in development and testing. Information is for reference only and does not replace professional consultation. Data may contain inaccuracies. Consult a qualified professional.

If you notice an error, please email buildingclubinfo@gmail.com.

Inspection progress0 of 7
0%

Surface preparation and substrate readiness

Critical item

Per ASTM D4258 (Standard Practice for Surface Cleaning of Concrete for Coating), all concrete surfaces receiving waterproofing must be clean, sound, and free of contaminants. ASTM D4259 (Standard Practice for Abrading Concrete) covers mechanical surface profiling. Concrete must be cured per ACI 308R (Guide to External Curing of Concrete) to a minimum 28-day strength before membrane application. Surface moisture content must not exceed manufacturer limits, typically below 5% per ASTM D4263 (Standard Test Method for Indicating Moisture in Concrete by the Plastic Sheet Method).

Below-grade waterproofing

Critical item

Per IRC R406.1, concrete and masonry foundation walls that retain earth and enclose habitable or usable space below grade must be waterproofed. IRC R406.2 requires waterproofing to extend from the top of the footing to the finished grade. Liquid-applied membranes must meet ASTM D6083 (Standard Specification for Liquid Applied Acrylic Coating Used in Roofing) or ASTM C836 (Standard Specification for High Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane). Sheet membranes must meet ASTM D4068 (Standard Specification for Chlorinated Polyethylene (CPE) Sheeting for Concealed Water-Containment Membrane). Dampproofing alone per IRC R406.1 is only permitted for non-habitable spaces.

Above-grade moisture barriers and weather-resistive barriers

Critical item

Per IBC Section 1402.2 and IRC R703.1, a weather-resistive barrier (WRB) is required behind all exterior wall coverings. The WRB must be applied shingle-fashion with upper layers overlapping lower layers per IRC R703.2. Window and door openings must be flashed per ASTM E2112 (Standard Practice for Installation of Exterior Windows, Doors and Skylights). Building paper must meet ASTM D226 Type I (asphalt-saturated felt) or housewrap must meet ICC-ES AC38 criteria for water resistance, air resistance, and vapor permeability.

Wet area waterproofing for bathrooms and showers

Critical item

Per the TCNA Handbook (Tile Council of North America), shower receptors and wet area floors must be waterproofed with a membrane meeting ANSI A118.10 (Standard Specification for Load Bearing, Bonded, Waterproof Membranes for Thin-Set Ceramic Tile and Dimension Stone Installation) or ANSI A118.12 (Standard Specification for Crack Isolation Membranes for Thin-Set Ceramic Tile and Dimension Stone Installations). The IPC (International Plumbing Code) Section 417.5.2 requires shower pan liners to be tested watertight by filling to the threshold for 24 hours. Membrane must extend a minimum of 3 inches above the finished threshold per IPC 417.5.2.

Deck and balcony waterproofing

Critical item

Per IBC Section 1507.1, waterproofing for walking decks over occupied space must be an approved system. IRC R507.1 covers exterior deck requirements. IBC Section 1604.8.3 requires minimum 1/4 inch per foot slope for exterior decks and balconies to ensure positive drainage. ASTM C957 (Standard Specification for High-Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane With Integral Wearing Surface) governs traffic-bearing deck membranes. Per IRC R507.2.2, wood framing supporting waterproofed decks must be preservative-treated or naturally durable.

Flashing and transition detailing

Critical item

Per IRC R703.8, approved corrosion-resistant flashing must be installed at all locations where required to prevent moisture from entering the wall assembly. ASTM E2112 (Standard Practice for Installation of Exterior Windows, Doors and Skylights) details proper flashing sequencing at openings. IRC R703.4 requires flashing at the intersection of exterior walls and roofs. All flashing must be self-adhering, metal, or a combination system, and must be integrated with the WRB in shingle-fashion per IRC R703.2.

Drainage and weep systems

Per IRC R405.1, drains must be installed around foundations enclosing habitable or usable below-grade spaces. Footing drains must be gravel-bedded and sloped to discharge by gravity or to an approved sump per IRC R405.1. For above-grade wall systems, IRC R703.7.6 requires weep holes in the bottom course of masonry veneer spaced no more than 33 inches on center. A minimum 1-inch air space or drainage mat per IRC R703.7.4 is required behind masonry and adhered veneer to allow moisture to reach the weep system.

Checklist for inspecting waterproofing and moisture barrier installation per ICC, ASTM, and manufacturer standards.

Reference Standards

  • IBC Chapter 14 — Exterior Walls
  • IRC R406 — Foundation Waterproofing
  • ASTM D6083 — Liquid Applied Acrylic Coating for Waterproofing
  • ASTM D4068 — Sheet Waterproofing for Below-Grade
  • ASTM C836 — High Solids Content Cold Liquid-Applied Elastomeric Waterproofing
  • Tools Needed

  • Moisture meter
  • Mil gauge (for membrane thickness)
  • Infrared thermometer
  • Adhesion tester
  • Tape measure